Pump Control / Grit / Screening Building |
|
Collapsed Gutter on West wall |
|
|
|
|
|
|
|
|
|
|
Concrete at Pump / Grit / Screening Building |
|
soil subsidence undermining concrete flatwork on south wall |
|
|
|
|
|
|
|
|
|
|
Pump / Grit / Screening |
|
Looking east |
|
|
|
|
|
|
|
|
|
|
East side Pump / Grit / Screening |
|
concrete sidewalk differential settlement |
|
|
|
|
|
|
|
|
|
|
Sidewalk on North side of screw pumps |
|
local settlement creating ponding problems |
|
|
|
|
|
|
|
|
|
|
|
East wall of pump control building |
|
|
|
|
|
|
|
|
|
|
|
|
|
New touch screen interface for pump VFD control |
|
need new sensor; must presently operate pumps in manual mode |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pump control / Grit / Screening Roof |
|
|
|
|
|
|
|
|
|
|
|
|
|
Influent flowmeter read-out |
|
new ultrasonic doesn't have data logging capabilites. Data recorded on paper charts in lab building. |
|
|
|
|
|
|
|
|
|
|
Grit removal basin |
|
Oil sock in response to diesel spill containment. Aeration blowers are presently off to prevent stirring of fuel. |
|
|
|
|
|
|
|
|
|
|
|
|
Wet well. |
|
Level sensor leads need to be routed in conduit |
|
|
|
|
|
|
|
|
|
|
Lift Station pumps |
|
two 40 hp; one 25 hp; one 25 hp removed |
|
|
|
|
|
|
|
|
|
|
Effluent clarifier |
|
Former chlorine contact / dosing basin |
|
|
|
|
|
|
|
|
|
|
|
|
|
Concrete settlement near effluent chamber |
|
|
|
|
|
|
|
|
|
|
|
|
minor erosion due to runoff |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Facia on chlorine building |
|
Wood facia in need of painting (typ. through site). |
|
|
|
|
|
|
|
|
|
|
North Wall Chlorine Building |
|
|
|
|
|
|
|
|
|
|
|
|
North Wall Tertiary Filtration Building |
|
|
|
|
|
|
|
|
|
|
|
|
|
Digester Concrete |
|
Typical spalling at aerobic digester. Extensive concrete failure. |
|
|
|
|
|
|
|
|
|
|
|
Digester Concrete / Gates |
|
gate frames are largely inoperable due to concrete displacement. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Lab / Blower building |
|
West overhead door / masonry crack at lintel. |
|
|
|
|
|
|
|
|
|
|
South Wall Lab / Blower building |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Secondary Clarifier |
|
minor paint touch-up required |
|
|
|
|
|
|
|
|
|
|
|
|
Effluent trough from Aeration Basins to Secondary Clarifier |
|
concrete settlement |
|
|
|
|
|
|
|
|
|
|
|
Aeration Basins - North Wall |
|
Grade settlement along north wall undermining walkway. |
|
|
|
|
|
|
|
|
|
|
Primary Clarifier pump control / Mixing Aeration / Chem Feed Building |
|
|
|
|
|
|
|
|
|
|
|
|
|
Aeration Basins |
|
Air Line leak in north cell |
|
|
|
|
|
|
|
|
|
|
South Cell - Aeration Basin |
|
sludge holding in South Cell |
|
|
|
|
|
|
|
|
|
|
|
|
|
Tree growing in transfer gate of Cell #2 |
|
EMC to remove this summer |
|
|
|
|
|
|
|
|
|
|
|
|
Primary Clarifiers |
|
fill, grade and reseed |
|
|
|
|
|
|
|
|
|
|
Rehabbed South Primary Clarifier |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power leads for South PC drive exposed |
|
Wires to be place in trenched conduit from West Building |
|
|
|
|
|
|
|
|
|
|
|
West Control / Chem Feed Building |
|
|
|
|
|
|
|
|
|
|
|
|
|
Blower intake at Chem Feed Building |
|
|
|
|
|
|
|
|
|
|
|
|
Control Room @ Chem Feed Building |
|
|
|
|
|
|
|
|
|
|
|
|
|
Drive between PC's and Aeration Basins |
|
Need add'l base rock and a seal coat |
|
|
|
|
|
|
|
|
|
|
Primary Blowers in Lab / Blower Building |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Starter Panels - Replacing old drives with new VFD's through attrition |
|
|
|
|
|
|
|
|
|
|
|
|
Old starter panels with new VFD's for blowers |
|
|
|
|
|
|
|
|
|
|
|
|
Old Aquatrol status board in Lab |
|
Board data displays non functioning. System obsolete; components not available. Recommend replacing with PC based SCADA control system. |
|
|
|
|
|
|
|